Cart Total Items (0)

Cart

-20%

UPS EVO DSP PLUS 1200-2400-3600 RACK / TOWER IEC TOGETHER ON

UPS EVO DSP PLUS 1,200 RACK TOWER – Power 1,200-2400-3600 VA PF 0,9. On Line Technology (VFI) DSP, 94% Efficiency, Input / output 230 / 230Vac 50 / 60Hz, IEC Output Sockets.

UPS EVO DSP PLUS 1,200-2400-3600 RACK TOWER – Power 1,200 VA PF 0,9. On Line Technology (VFI) DSP, 94% Efficiency, Input / output 230 / 230Vac 50 / 60Hz, 8 IEC C13 sockets, dimensions 43.8×8.8×31 cm (2U), weight 12 Kg, bacup time 10 min, including 2 batteries for 12Vdc 9AH. Positioning in 19 “rack or tower, multifunction graphic LCD display, static bypass, hot swap battery, EPO connector, USB and RS232 communication ports, for UPS control and on / off programming via the free TecnoManager software. SNMP card or Dry Contact (optional).

Reviews

There are no reviews yet.

Be the first to review “UPS EVO DSP PLUS 1200-2400-3600 RACK / TOWER IEC TOGETHER ON”

Votre adresse e-mail ne sera pas publiée. Les champs obligatoires sont indiqués avec *

Fiche technique

CodeUPS EVO DSP PLUS 1,200-2400-3600 RACK TOWER
Nominal Power1.200 VA
Active Power1.080 W
Power Factor0,9
TechnologyOn-Line Double Conversion transformerless (VFI-SS-111)
CoolingFan cooling
Audible Noise< 45 dBA at 1 m
Dimension (UPS) WxHxD43,8x8,8x31 cm
Dimension (with packing) WxHxD50x18x40 cm
Weight12 Kg
PositioningTower positioning or Into 19’’ rack (2U)
Input
Nominal Voltage208Vac/220Vac/230Vac/240Vac
Input Voltage Range110-300Vac
Nominal Frequency50/60 Hz (selectable)
Number of phases1Ph+N
Input power factor0,99
Output
Overload Capability110% only audible warning, 110-130% for 30 sec, >130% for 100 ms
Transfer time0 ms (On-Line)
Number of phases1Ph+N
Nominal voltage208Vac/220Vac/230Vac/240Vac (selectable)
Static voltage Regulation at %100 linear load (On-Line and battery mode)±1%
Voltage THD at rated linear load<2% (linear load), <8% (non-linear load)
Crest factor3:1
Frequency50/60 Hz (selectable)
Free running frequency±0,2 Hz
Inverter waveformSinewave
Efficiency94%, calculated in double conversion modeto 100% load according to standard 62040-3
Battery
TypeLead acid, sealed, maintenance free
Backup time (Typical)10-30 min
Environmental specification
Working TemperatureFrom 0 to 55 °C (recommended from 20 to 25 °C)
Humidity< 95% without condensation
Maximum Altitude3000 m
IP ProtectionIP20
CertificationsCE (Standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classification IEC EN 62040-3)
×