Cart Total Items (0)

Cart

UPS EVO DSP PLUS RACK MOUNT 10.0 – PF 0.9

UPS EVO DSP PLUS 10.0 PF 1 – Power 10KVA. On Line Technology (VFI) DSP, 94% Efficiency, Input / output 230 / 230Vac 50 / 60Hz, dimensions 19×68.8×44.2 cm, weight 23 Kg,ready to install 16 12V 7-9-11Ah batteries.

UPS EVO DSP PLUS RACK MOUNT 10.0 – Power 10 KVA PF 0.9. On Line Technology (VFI) DSP, 94% Efficiency, Input / output 230 / 230Vac 50 / 60Hz, dimensions 43.8×13.3×58 cm (3 Rack units), weight 18 Kg, does not include batteries, for bacup time add external battery boxes. Multifunction graphic LCD display, static bypass, EPO contact for emergency shutdown, USB and RS232 communication ports for UPS control and on / off programming via the free TecnoManager software. SNMP, Dry Contact or MODBUS card (optional).

Reviews

There are no reviews yet.

Be the first to review “UPS EVO DSP PLUS RACK MOUNT 10.0 – PF 0.9”

Votre adresse e-mail ne sera pas publiée. Les champs obligatoires sont indiqués avec *

Fiche technique

CodeFGCEVDP10MMRM/00
Nominal Power10 KVA
Active Power10 KVA
Power Factor0,9
TechnologyOn-Line Double Conversion transformerless (VFI-SS-111)
CoolingFan cooling
Audible Noise< 48 dBA to 1 m
Dimension (UPS) WxHxD43,8x13.3x58 cm (3U)
Dimension (with packing) WxHxD59x26x78,5 cm
Weight18 Kg
Equipped With1 serial cable, Tecnomanager software and 2 metal handle for 19’’ Rack cabinet mounting
Input
Nominal Voltage208Vac/220Vac/230Vac/240Vac
Input Voltage Range176Vac-300Vac from 50% to 100% load, 110Vac-300Vac from to 50% load
Nominal Frequency50/60 Hz (selectable)
Number of phases1Ph+N
Input power factor0,99
Output
Transfer time0 ms (On-Line)
Number of phases1Ph+N
Nominal voltage208Vac/220Vac/230Vac/240Vac
Static voltage Regulation at %100 linear load (On-Line and battery mode)±1%
Crest factor3:1
Frequency50/60 Hz (selectable)
Inverter waveformSinewave
Efficiency94%, calculated in double conversion mode at 100% load to 100% load according to standard 62040-3
Frequency stability±0,1 Hz
Voltage THD<3% (linear load), <6% (non-linear load)
Overload capability (Battery mode)110% for 30 seconds, 130% for 10 seconds, >130% for 1 second
Overload capability (On-line mode)110% for 10 minutes, 130% for 1 minute, >130% for 1 second
Battery
Extended autonomyExternal Battery Box (optional)
Batteries number16 (inside the external Battery Box, for UPS operation)
Battery charge time (typical)6-8 hours
Environmental specification
Working TemperatureDa 0 a 55 °C (recommended from 20 to 25 °C)
Humidity< 95% without condensation
Maximum Altitude3000 m
IP ProtectionIP20
CertificationsCE (standards: Low Voltage Directive IEC EN 62040-1; EMC Directive IEC EN 62040-2; classification IEC EN 62040-3)
×